TL;DR: As carriers retire copper phone lines, fire and alarm panels that report through a DACT on POTS lines need a new path to the monitoring center. That usually means a communicator listed for fire use (cellular, IP, or dual-path), installed to the edition of NFPA 72 your jurisdiction has adopted and approved by the AHJ. Contractors who build an account list and schedule changeouts now control the timing.
Copper retirement is happening market by market, not on one national cutoff date. Every monitored fire or intrusion account still dialing out over phone lines will need a new communicator, and you can replace them on your schedule or wait for the carrier to set it for you.
Why are copper phone lines going away?
Carriers are retiring copper because maintaining it costs more every year and fewer customers use it. AT&T has said it plans to shut down copper-based services across most of its U.S. territory by the end of 2029, with California handled separately, according to Light Reading’s December 2024 coverage of the company’s plans.
Regulators have made that process easier. On March 26, 2026, the FCC unanimously adopted an order easing the process of decommissioning copper networks, according to Broadband Breakfast. The order removed some network-change filing requirements and gave carriers blanket authority to stop offering legacy copper voice and low-speed broadband to new customers. Carriers still need FCC approval to discontinue service for existing customers, and they still have to send discontinuance notices.
The decline is already large. U.S. copper lines fell from 122 million in 2010 to about 36 million, according to FluentStream’s summary of FCC voice subscription data.
For fire and security contractors, timing varies by carrier, wire center, and state, but every monitored account on a copper line is on a clock. Some building owners will get a notice with months of lead time. Others will find out when a line is moved to a carrier box or a VoIP service and the panel stops communicating cleanly.
The carrier will tell the building owner. It won’t tell the fire alarm contractor, and that gap is the reason to get ahead of it.
What breaks when a fire alarm DACT loses its phone line?
A digital alarm communicator transmitter (DACT) was built to dial out over two analog phone lines, and any change to those lines can stop signals from reaching the monitoring center. Three things can happen:
- The line disappears. The panel reports a communication trouble, and if both lines are gone, signals stop reaching the monitoring center. The building is still protected locally, but no one off-site knows about an alarm.
- The line is converted to VoIP. This is the quieter failure. The phone still gets a dial tone, so the owner assumes nothing changed. But VoIP compresses audio, and DACT signals are data sent as tones. The Minnesota State Fire Marshal’s guidance states that VoIP “is not recommended for transmitting fire alarm signals because the information being sent is data and not voice.” Signals can arrive garbled, late, or not at all.
- The line moves to a carrier-supplied replacement box. Some carriers offer devices that emulate a phone line over wireless or fiber. Whether one of those is acceptable for a fire alarm depends on its listing, its backup power, and what your AHJ will approve. Don’t assume it qualifies because the carrier installed it.
The failure shows up as a trouble signal or a missed alarm, not a warning letter. That’s why it pays to find these accounts before the carrier does.
What can replace POTS lines for fire alarm monitoring?
Three types of communicators cover most POTS replacements on commercial fire and security panels: cellular, IP, and dual-path. All three need to be listed for the application and accepted by the monitoring center and the AHJ.
| Option | How it reports | Where it fits | Things to check |
|---|---|---|---|
| Cellular communicator | Sends signals over a carrier cellular network | Buildings without dependable internet, or where the owner’s network is off-limits | Signal strength at the panel, antenna placement, carrier network in that market |
| IP communicator | Sends signals over the building’s internet connection | Sites with a stable, managed network and IT cooperation | Network uptime, firewall rules, who owns the router and its backup power |
| Dual-path communicator | Uses cellular and IP together, with each path backing up the other | Most commercial fire accounts, and anywhere the AHJ wants two paths | Both of the above, plus how the monitoring center reports a failed path |
Dual-path units are the default choice on a lot of commercial fire work because they remove the single point of failure. If the building’s internet goes down, cellular carries the signal, and the reverse.
Many communicators connect to the panel’s existing dialer terminals and convert the DACT output, which means the panel itself often stays in place. Others connect through a panel-specific interface. Compatibility depends on the panel make and model, so confirm it before you quote. If the panel itself is locked or failing, our guide to taking over an existing alarm system covers when a panel swap makes more sense.
Your SDS franchise team can help match a communicator to the panel and pull the listing and installation documentation. The design and the AHJ submittal stay with the contractor.
Fire communicator options in the Security Data Supply lineup include Napco StarLink Fire and Alula (M2M) fire communicators, along with panel-native IP dialers from manufacturers such as Fire-Lite, Silent Knight, and Potter. Confirm the listing for the specific panel before you quote, and ask your franchise team what they keep on hand.
What will NFPA 72 and the AHJ look at?
NFPA 72 no longer requires two phone lines, but what you can install depends on the edition your jurisdiction has adopted and how your AHJ applies it. The Minnesota State Fire Marshal notes that NFPA 72 moved to “a less prescriptive and more performance based” approach for communication methods, and that a DACT can use one phone line plus a secondary path that is not a second phone line. Cellular, radio, and IP-based technologies are recognized options, and many cellular and radio products provide multiple communication paths that eliminate the need for phone lines.
Before you swap a communicator on a fire system, have answers to these five questions:
- Is the communicator listed for fire alarm use with the panel you’re connecting it to?
- How are the communication paths supervised, and how fast does the monitoring center get a trouble if a path fails?
- What provides secondary power to the communicator, and does your battery calculation include it?
- Does the AHJ require a permit, plan review, or acceptance test for a communicator change?
- Does the monitoring center support the format and the product you plan to install?
Question three gets missed often. A communicator draws current in standby and in alarm, and it has to stay up on battery like everything else on the system. If you add one, rerun the battery calculation. Our post on fire alarm battery backup calculations walks through the method.
This post explains the questions to ask. It doesn’t interpret code for your jurisdiction. When in doubt, ask the AHJ before you order equipment.
How do you survey a site before swapping a communicator?
A ten-minute survey before the install saves a second trip. Every replacement should start with the same checks:
- Measure cellular signal at the panel, not in the parking lot. Fire alarm panels live in electrical rooms, basements, and riser closets, which are the worst places in a building for cellular reception. Use the manufacturer’s signal test procedure or a meter. If the reading is weak, plan for a remote antenna and the cable run to get it somewhere better.
- Confirm the panel and the interface. Record the panel make, model, and firmware, and check whether the communicator connects to the dialer terminals or needs a specific interface module. Older panels sometimes need a different approach.
- Check the enclosure and power. Is there room in the panel can, or will the communicator need its own enclosure? Is there a power source and battery capacity for it, or does it need a separate power supply?
- Find out who owns the network. If you’re considering IP or dual-path, talk to whoever manages the building’s network. You need a port, a stable connection, and someone who won’t unplug the switch during a remodel.
- Pull the current monitoring information. Account number, receiver format, and monitoring center contact. The account has to be reprogrammed and tested end to end after the swap.
Bring that survey to the counter and the conversation about which communicator fits takes minutes, not a series of callbacks.
How should you plan a changeout across all of your accounts?
Treat the POTS sunset as a project with an account list, not a string of service calls.
- Build the account list. Pull every monitored fire and intrusion account that still reports over phone lines. Your monitoring center can often export accounts by communication format.
- Rank by risk. Put fire accounts, buildings where you know the line has already changed, and owners who’ve mentioned carrier letters at the top.
- Group by geography and panel type. Batching installs by area and by panel model cuts drive time and lets you stock the right parts once.
- Talk to the owner before the carrier does. A short letter or call explaining the change, the timeline, and the cost lands better from you than a trouble signal at 2 a.m.
- Quote the monthly service along with the hardware. Cellular and dual-path communicators usually carry a recurring service fee. That fee is a reason to talk about a monitoring and service agreement, not something to bury in the install price.
- Order in batches. Give your local franchise a forecast so the communicators, antennas, and enclosures are ready when your crew needs them.
A changeout is also a natural point to put recurring revenue on accounts that didn’t have it. Our post on how security contractors expand revenue streams covers the bigger picture.
What to bring to the counter for a communicator replacement
Walk in with the information that answers the compatibility questions, and the quote moves fast. For each account or batch, bring:
- Panel make, model, and firmware version, plus a photo of the dialer terminals if you have one.
- Current communication path: two POTS lines, one line, VoIP, or a carrier box.
- Signal survey results at the panel and any antenna run you expect.
- Monitoring center requirements, including the receiver format they support.
- Number of accounts if you’re planning a batch, so the franchise can plan stock.
Security Data Supply franchises are locally owned, and their teams are trained on the fire and intrusion equipment they distribute. They can help you narrow the communicator choice, find the accessories, and pull the documentation your AHJ will ask for. Browse the Fire and Intrusion categories, or use our fire alarm installation checklist before the next job.
Ready to plan your changeout? Bring your account list to your local SDS franchise team.
Frequently asked questions
What replaces POTS lines for fire alarm monitoring?
Most fire alarm panels that report over POTS lines are moved to a cellular, IP, or dual-path communicator listed for fire alarm use. Dual-path units, which use cellular and IP together, are common on commercial fire accounts because each path backs up the other. The AHJ and the monitoring center must accept the product and the installation.
Can a fire alarm panel use a cellular communicator as its only communication path?
It depends on the NFPA 72 edition your jurisdiction has adopted, the communicator’s listing, and how your AHJ applies the code. NFPA 72 has moved to a performance-based approach that recognizes cellular, radio, and IP technologies, and some products provide multiple paths on their own. Confirm with the AHJ before you design around a single cellular path.
Does the fire alarm panel need to be replaced when copper lines go away?
Often it doesn’t. Many communicators connect to the panel’s existing dialer terminals and convert the DACT output. Compatibility depends on the panel make, model, and firmware, so confirm it with the communicator manufacturer’s documentation before you quote.
Will a fire alarm DACT work on a VoIP line?
It may connect, but it is not a dependable path. VoIP compresses audio, and DACT signals are data sent as tones, so signals can be garbled or lost. The Minnesota State Fire Marshal’s guidance says VoIP is not recommended for transmitting fire alarm signals.
Do I need to update the battery calculation after adding a communicator?
Yes. A communicator draws current in standby and in alarm, and it has to stay powered on battery for the required duration. Add its current draw from the manufacturer’s data sheet to your standby and alarm totals and confirm the battery size still works.
How do I check cellular signal before installing a communicator?
Test at the panel itself, using the manufacturer’s signal test procedure or a cellular meter. Electrical rooms and basements often have weak reception. If the reading is low, plan a remote antenna and the cable run before the install day.
When will my customers’ copper lines be shut off?
Timing varies by carrier, state, and wire center, and carriers must notify customers before discontinuing service. AT&T has said it plans to retire copper across most of its territory by the end of 2029. Treat any monitored account on copper as one that needs a plan now.
About the author
Ron Broussard is Chief Executive Officer of Security Data Supply and has more than 30 years of experience in the security industry. He has held executive leadership roles across distribution and manufacturing, giving him a broad perspective on the challenges contractors, integrators, and distributors face every day. At Security Data Supply, he guides the company’s franchise network, vendor relationships, and long-term growth strategy.
Methodology
This article draws on public reporting about carrier copper retirement and FCC action, state fire marshal guidance on fire alarm signal transmission, and the experience of Security Data Supply franchise teams. Carrier timelines and code requirements change and vary by jurisdiction. Confirm the adopted NFPA 72 edition and communicator requirements with your AHJ, and confirm product compatibility with the manufacturer’s documentation.
Sources and further reading
- Light Reading: How and when AT&T will kiss copper goodbye
- Broadband Breakfast: FCC adopts copper retirement, call center onshoring orders
- FluentStream: The FCC just accelerated the POTS copper sunset
- Minnesota State Fire Marshal: Fire alarm signal transmission